Download PDFOpen PDF in browserAn Experimental Analysis to Check Accuracy of DGA.....8 pages•Published: August 5, 2017AbstractAnalysis of Dissolved gas method is very sensitive and reliable method for detection of internal fault in power transformer. One of the most used method for DGA is duval triangle method. Duval triangle is not considering two combustible gases like, ethane so, Duval triangle method has low accuracy for fault interpretation. Then, Duval pentagonal method is used for fault detection in power transformer. In this paper, we have get data for power transformer from Torrent Power Ltd. This experiment has done on various 20 power transformer rating of 15MVA,21kV/400kV. But, In this paper, We have shown six data of fault in case study and found fault by Duval Triangle method and Duval pentagonal method. Then, we will verify this fault interpretation with actual fault. And, we will see that Duval Pentagonal method have higher accuracy (above 80%) for fault interpretation.Keyphrases: dissolved gas analysis (dga), duval pentagon, fault diagnosis, power transformers In: Ajitkumar Shukla, J. M. Patel, P. D. Solanki, K. B. Judal, R. K. Shukla, R. A. Thakkar, N. P. Gajjar, N. J. Kothari, Sukanta Saha, S. K. Joshi, Sanjay R. Joshi, Pranav Darji, Sanjay Dambhare, Bhupendra R. Parekh, P. M. George, Amit M. Trivedi, T. D. Pawar, Mehul B. Shah, Vinay J. Patel, Mehfuza S. Holia, Rashesh P. Mehta, Jagdish M. Rathod, Bhargav C. Goradiya and Dharita K. Patel (editors). ICRISET2017. International Conference on Research and Innovations in Science, Engineering and Technology. Selected Papers in Engineering, vol 1, pages 394-401.
|